PROTEKSI PASIF KEBAKARAN PADA STUKTUR PENOPANG PIPA PROSES DENGAN EPOXY INTUMESCENT

Authors

  • Sulardi Sulardi Sekolah Tinggi Teknologi Minyak dan Gas Bumi (STT Migas) Balikpapan

DOI:

https://doi.org/10.36277/identifikasi.v6i1.115

Keywords:

epoxy intumescent, passive fire protection.

Abstract

The purpose of this study is to provide a description of passive fire protection material specifications that are suitable and suitable for pipe rack protection, pipe support and hanger pipe support hotline hydrocarbons and working methods of application of epoxy intumescent material. The research method used is the applied research method with a case study approach to the difficulty of handling sub-standard conditions at the Balikpapan I refinery. The research was conducted for 6 months and an observation period of 2 years. The results showed that the epoxy intumescent material specifications could be applied well and safely with an application thickness of 8.13 mm for a 1.5-hour fire rating according to API Standard 2218 and covered insurance findings at the Balikpapan refinery 1. The success of the intumescent epoxy application replaced the fireproofing material based on cementitious this can be replicated to overcome similar problems at other process unit refineries that experience similar problems.

References

API Standard 560, 2001, Fired Heaters for General Refinery Services, 3rd edition, American Petroleum Institute 1220 L Street, Northwest Washington, DC. 20005
API Standard 650, 2013, Welded Tanks for Oil Storage, 13 Edition, American Petroleum Institute Publishing Services, 1220 L Street, NW, Washington, DC 20005
API Standard 2218, 1999, Fireproofing Petrochemical Processing Plant, API Publication 2 Edition, 1220 L Street, NW, Washington, DC 20005
David S.J Stan Jones, 2006, Handbook Of Petroleum Processing, Published by Springer, P.O. Box 17, 3300 AA Dordrecht, The Netherlands.
Doc. No. PS-250-1384-001-E Rev.R, 1994, JGC Project Specification Job Code 0-8700, Balikpapan I Project Upgrading.
Gathot Heri Sudibyo, Nor Intang Setyo, 2010, Pengaruh Fire Proofing pada Balok Beton Pasca Bakar, Jurnal Rekayasa Vol. 6 No. 2.
Mohinder L Nayyar, 2000, Piping Handbook, MC Graw Hill Book New York San Francisco Washington, D.C.
Peraturan Pemerintah Republik Indonesia No. 11 Tahun 1979 tentang Pengolahan dan Pemurnian Minyak Bumi. Jakarta.
Sulardi, 2019, Keselamatan Industri Pengolahan Minyak (K3 Kilang), Nusa Litera Inspirasi, Ceirebon, Jawa Barat.
Undang-Undang Nomor 1 Tahun 1970 tentang Keselamatan Kerja.